Comparison of R-22 Alternatives
|
| Properties |
R-22 |
R-417A |
R-407C |
R-410A |
| Composition |
R-22 |
134a/125/600 |
134/125/32 |
125/32 |
| ODP |
0.05 |
0 |
0 |
0 |
| Boiling Point (F') |
-41.4 |
-43.3 |
-46.4 |
-59.9 |
| Temperature Glide (R) |
0 |
10.0 |
13.3 |
<0.4 |
| Critical Temperature |
205 |
194 |
187 |
162 |
Condensing Temperature
at 375 psi (absolute) |
145 |
154 |
136 |
109 |
| Refrigeration Capacity (%) |
100 |
97 |
100 |
142 |
| C.O.P. (%) |
100 |
112 |
95 |
95 |
| Discharge Gas Temp. (R) |
- |
-16.2 |
-18 |
-10.8 |
| Lubricants |
MO,AB,POE |
POE |
POE |
10% Lower Power Consumption Than R407C
|
| Measurement |
R-417A |
R-407C |
| Ambient Temperature |
71.6"F |
71.60F |
| Condensing Temperature |
105.0"F |
102.6"F |
| High Pressure |
197 psia |
214 psia |
| Evaporator Air Off
Temperature |
48.1"F |
47.20F |
| Refrigerant Charge |
3 lb 6 oz |
3 lb 1oz |
| Power Consumption |
1.65 kW |
1.83 kW |
R-417A is a zeotropic three-component blend, which we recommend, be
transferred from the cylinder in the liquid phase. In any operational
leak scenario, the system may be topped up with R-417A without
significant effect on performance.
R-417A is an effective refrigerant for process cooling. R-417A has
demonstrated its effectiveness at higher temperatures, giving the added
benefit of lower discharge temperatures.
R-417A is a well-suited, proven refrigerant for cold store
applications. R-417A works well from margarine and fruit storage at
around +3ºC, to medium temperature storage at -30ºC. In many instances
lower compressor discharge temperatures have been reported which can be
a bonus where systems are running close to the recommended maximum.
The information contained in this document is given in
good faith based on our current knowledge. It is only an indication and
is in no way binding, particularly as regards infringement of or
prejudice to third party rights through the use of our products.
RMS of Georgia, LLC will be pleased to give further
advice and assistance, but customers must satisfy themselves by
appropriate testing if necessary that the product is suitable for their